Use in explosion-proof areas
18 265Dx, 265VS IM/265D/V-EN-02
Pos: 7.16 /Übersc hriften/1.1/1-spal tig/V - Z/Zündschut zart Eigensicherhei t, druckfeste Kapselung und ener giebegrenzte Bet riebsmittel @ 3\mod_1157 964815781_3101.doc @ 41176
2.6 Explosion protection types "Intrinsically safe", "Flameproof enclosure", and "Limited energy
equipment"
Pos: 7.17 /Ex-tec hnische Sicherheits hinweise/Druck/ Druckmessumformer/Al lgemein/Zündschutz art Eigensicherheit , druckfeste Kapsel ung und energiebegrenzte Bet riebsmittel @ 3\m od_1157963542656_3101.doc @ 41071
Alternative certification:
Intrinsically safe (Category 1/2, EEx i) or
Flameproof enclosure (Category 1/2, EEx d), or
Limited energy equipment (Category 3, EEx nL)
Important
Prior to commissioning, the selected type of explosion protection (only one may be selected)
must be permanently marked in the appropriate box on the name plate. Once selected, the
type of explosion protection may not be changed.
If a supply is not intrinsically safe, or the transmitter has been fed in a way that is not intrinsically
safe, the explosion protection type "Intrinsically safe" is no longer valid.
Caution - Risk
Failure to observe this information will have an adverse effect on explosion protection.
Appropriate cable and wire entries must be used depending on the explosion protection type
selected:
Explosion protection type Cable gland
(minimum requirement)
II 1/2 G EEx i
II 1/2 D EEx i
IP 54
IP 6x
II 1/2 G EEx d
II 1/2 D EEx d
EEx d
EEx d and IP 6x
II 3 G EEx n
II 3 D EEx n
EEx e
EEx e and IP 6x
Pos: 7.18 /Übersc hriften/1.1/1-spal tig/J - L/Kanadischer Standard CSA - explosion pr oof @ 3\mod_1157964979734_31 01.doc @ 41197
2.7 Canadian Standards Association (CSA): "Explosion-proof"
Pos: 7.19 /Ex-tec hnische Sicherheits hinweise/Druck/ Druckmessumformer/Al lgemein/Kanadischer Standard CSA - explosion pr oof @ 3\mod_1157963634125_ 3101.doc @ 41092
Caution - Potential damage to parts
Transmitters with LCD displays must not be used in etherized atmospheres.