Configuration
IM/265D/V-EN-02 265Dx, 265VS 59
8.6.1.7 (Damping) parameter
Setting for an additional time constant, between 0 s and 60 s, in increments of 0.001 s.
8.6.1.8 "ALARM CURRENT" parameter
Not with fieldbus transmitters
8.6.1.9 "DISPLAY" parameter
Selection (non-volatile) for LCD display values 1, 2, or 3 (permanent display)
The following measured values can be set:
Output signal in physical unit
265Dx: Current measured value for differential pressure, or variable derived from this, such
as flowrate / level, with customized unit in each case
265Vx: Current measured value for absolute pressure; corresponds to "OUT" with
PROFIBUS PA
Setting changes under "OUT 0 %" and "OUT 100 %"; desired unit under "UNIT_OUT"
Percentage value of output signal
Output current (not with fieldbus transmitters)
8.6.1.10 "UNIT - p/dp" parameter
Selection list of pressure units for the pressure/differential pressure detected by the sensor, for
LCD display code no. 8 under "VIEW"
8.6.1.11 "UNIT - OUT" parameter
"Selection list" of "OUT" units (for output variables, e.g., kg/h,
m, l/h, mbar), for LCD display
code no. 1 under "VIEW" or "DISPLAY"
8.6.1.12 "FUNCTION" parameter
In this menu item, you can choose from the functions "linear", "square root", and "freely
programmable". The parameters, such as "zero reset", "lin./sq. root transition point", or
"individual values of the freely programmable characteristic", cannot be changed here. A
handheld terminal or graphical user interface (DTM) must be used in order to make changes.
8.6.1.13 "ADDRESS" parameter
Only with fieldbus transmitters