Actual signals and parameters 247
4405
AI IN VERY LOW
0.00 … 100.00% 1 = 0.01% 0.00%
Supervision level for the secondary inlet pressure monitoring function. See parameter
4401 INLET PROT CTRL. Supervision level.
4406
DI STATUS INLET
NOT SEL
Selects the digital input for connection of a pressure switch at the pump/fan inlet. The
“normal” state is 1 (active). If the selected input switches to 0 (inactive), the action
defined by parameter 4401 INLET PROT CTRL is executed after the delay set by
parameter 4407 INLET CTRL DLY expires.
0 = NOT SEL – No digital input selected.
1 = DI1 – Pump/fan inlet pressure monitored through digital input DI1.
2 = DI2 – See selection DI1.
3 = DI3 – See selection DI1.
4 = DI4 – See selection DI1.
5 = DI5 – See selection DI1.
4407
INLET CTRL DLY
0.1 … 1800.0 s 1 = 0.1 s 60.0 s
Sets the delay after which the action defined by parameter 4401 INLET PROT CTRL is
taken on detection of low inlet pressure.
4408
INLET FORCED REF
-100.0 … 100.0% 1 = 0.1% 0.0%
This reference is used after detection of low inlet pressure. See parameter 4401 INLET
PROT CTRL.
WARNING! Make sure that it is safe to continue operation using this reference.
Group 44: Pump protection
Code Description Range Resolution Default S