Fieldbus control 303
Analog input – The analog input objects support the following features:
Analog Input actual value in engineering units
Low Alarm limit
Low Warning limit
High Warning limit
•High Alarm limit
Differential value for the hysteresis of the Alarms and Warnings
Change of State (COS) enabled
Alarm Enabled
Warning Enabled
Override value is received, but there is no action taken.
Binary input – The binary input objects support the following features:
Binary Input actual value
Normal / Alarm state specification
Alarm Enabled
Change of State (COS) enabled
Override value is received, but there is no action taken.
Analog output The analog output objects support the following features:
Analog Output value in engineering units
Override value is used to change the Analog Output value. It is not possible to
return to the previous value by removing the override. The override feature is
used only to change the value.
Binary output – The binary output objects support the following features:
Binary Output value
Override value is used to change the Binary Output value. It is not possible to
return to the previous value by removing the override. The override feature is
used only to change the value.