324 Fieldbus control
94 RESET FAULT Command by FLN to reset a faulted drive
(1 = RESET, 0 = NO).
Parameter 1604 must be set to COMM for FLN to
control this state.
The control input is rising-edge sensitive, so, once the
command is issued, this point automatically returns to its
inactive state. This “momentary” operation avoids any
need for an explicit command to clear the point before a
subsequent reset can be issued.
95 MBOX PARAM Sets the parameter to be used by the mailbox function.
96 MBOX DATA Sets or indicates the data value of the mailbox function.
97 MBOX READ Command by FLN to read the parameter value specified
by Point 95, MBOX PARAM. The parameter value is
returned in Point 96, MBOX DATA.
The control input is rising-edge sensitive, so, once the
command is issued, this point automatically returns to its
inactive state. This “momentary” operation avoids any
need for an explicit command to clear the point before a
subsequent reset can be issued.
98 MBOX WRITE Command by FLN to write the data value specified by
Point 96, MBOX DATA, to the parameter value specified
by Point 95, MBOX PARAM.
The control input is rising-edge sensitive, so, once the
command is issued, this point automatically returns to its
inactive state. This “momentary” operation avoids any
need for an explicit command to clear the point before a
subsequent reset can be issued.
99 ERROR
STATUS
1 of the 5 mandatory FLN points required for
compatibility with Siemens control systems. It has no
functionality in the drive application.
None
FLN Detailed Point Descriptions
Point Description
Drive
Parameter