EasyManua.ls Logo

ABB ACS320 - Page 52

ABB ACS320
442 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
52 Electrical installation
Frequency input
If DI5 is used as a frequency input, see section Frequency input on page 111 for how
to set parameters accordingly.
Connection example of a two-wire sensor
HVAC default, supply fan, return fan, cooling tower fan, condenser, booster pumps,
PFA control, internal timer, dual setpoint with PID, E-Clipse and dual setpoint with PID
and constant speeds macros (see section Application macros on page 79) use
analog input 2 (AI2). The macro wiring diagrams for these macros show the
connection when a separately powered sensor is used. The figure below gives an
example of a connection using a two-wire sensor.
Note: The sensor is supplied through its current output. Thus the output signal must
be 4…20 mA.
X1A
5 AI2 Process actual value measurement or reference,
4…20 mA, R
in
= 100 ohm
6GND
9 +24V Auxiliary voltage output, non-isolated,
+24 V DC, max. 200 mA
10 GND
P
I
4…20 mA

Table of Contents

Other manuals for ABB ACS320

Related product manuals