268 Actual signals and parameters
DI1 The function is activated/deactivated through digital input
DI1.1 = activation, 0 = deactivation.
The internal sleep criteria set by parameters 4023 PID
SLEEP LEVEL and 4025 WAKE-UP DEV are not effective.
The sleep start and stop delay parameters 4024 PID SLEEP
DELAY and 4026 WAKE-UP DELAY are effective.
1
DI2 See selection DI1.2
DI3 See selection DI1.3
DI4 See selection DI1.4
DI5 See selection DI1.5
INTERNAL Activated and deactivated automatically as defined by
parameters 4023 PID SLEEP LEVEL and 4025 WAKE-UP
DEV.
7
DI1(INV) The function is activated/deactivated through inverted digital
input DI1. 1 = deactivation, 0 = activation.
The internal sleep criteria set by parameters 4023 PID
SLEEP LEVEL and 4025 WAKE-UP DEV are not effective.
The sleep start and stop delay parameters 4024 PID SLEEP
DELAY and 4026 WAKE-UP DELAY are effective.
-1
DI2(INV) See selection DI1(INV).-2
DI3(INV) See selection DI1(INV).-3
DI4(INV) See selection DI1(INV).-4
DI5(INV) See selection DI1(INV).-5
All parameters
No. Name/Value Description Def/FbEq