Recommended annual actions by the user
DescriptionAction
Tightness of terminalsI
Dustiness, corrosion or temperatureI
Heat sink cleaningP
Recommended maintenance actions by the user
Years from start-upComponent
21181512963
Cooling
Main cooling fan
RRMain cooling fans
Auxiliary cooling fan
RRAuxiliary cooling fan
RRSecond auxiliary cooling fan (IP55, UL Type 12)
Aging
RRRControl unit battery (real-time clock)
RRControl panel battery (real-time clock)
Functional safety
I
See the maintenance inform-
ation of the safety function
Safety function test
20 years
Safety component expiry (Mission time, T
M
)
4FPS10000309652
Note:
• Maintenance and component replacement intervals are based on the assumption
that the equipment is operated within the specified ratings and ambient conditions.
ABB recommends annual drive inspections to ensure the highest reliability and
optimum performance.
• Long term operation near the specified maximum ratings or ambient conditions may
require shorter maintenance intervals for certain components. Consult your local
ABB Service representative for additional maintenance recommendations.
144 Maintenance