Frame
size
Cooling air flowHeat dissipationACS880-
11-…
FrontHeatsinkFrontHeatsink
m
3
/hm
3
/hWW
R8607401123056169A-3
R8607401413849206A-3
U
n
= 500 V
R3-3613918007A6-5
R3-3614023811A0-5
R3-36141280014A-5
R35236144429021A-5
R65249847578027A-5
R65249848663034A-5
R65249850757040A-5
R65249853907052A-5
R652498591164065A-5
R652498661494077A-5
R860740771918101A-5
R8607401002700124A-5
R8607401123056156A-5
R8607401363736180A-5
Terminal and entry data for the power cables
Input, motor and DC cable entries, maximum wire sizes (per phase) and terminal screw
sizes and tightening torques are given below. Ø = Maximum cable diameter accepted.
•
For the bottom plate hole diameters, see chapter Dimension drawings (page 201).
• The minimum specified wire size does not necessarily have sufficient current carrying
capacity at maximum load.
• The terminals do not accept a conductor that is one size larger than the maximum
specified wire size.
• The maximum number of conductors per terminal is 1.
L1, L2, L3, T1/U, T2/V, T3/W, UD+, UDC- terminalsCable entriesFrame
Tightening
torque
Max wire size
(solid/ stran-
ded)
Min wire size
(solid/ stran-
ded)
1)
Øpcs
N·mmm
2
mm
2
mm
1.716.00.5233R3
5.670.06.0453R6
184 Technical data