Frame
size
Cooling air flowHeat dissipationACS880-
11-…
FrontHeatsinkFrontHeatsink
m
3
/hm
3
/hWW
R8607401123056169A-3
R8607401413849206A-3
U
n
= 500 V
R3-3613918007A6-5
R3-3614023811A0-5
R3-36141280014A-5
R35236144429021A-5
R65249847578027A-5
R65249848663034A-5
R65249850757040A-5
R65249853907052A-5
R652498591164065A-5
R652498661494077A-5
R860740771918101A-5
R8607401002700124A-5
R8607401123056156A-5
R8607401363736180A-5
Terminal and entry data for the power cables
Input, motor and DC cable entries, maximum wire sizes (per phase) and terminal screw
sizes and tightening torques are given below. Ø = Maximum cable diameter accepted.
For the bottom plate hole diameters, see chapter Dimension drawings (page 201).
The minimum specified wire size does not necessarily have sufficient current carrying
capacity at maximum load.
The terminals do not accept a conductor that is one size larger than the maximum
specified wire size.
The maximum number of conductors per terminal is 1.
L1, L2, L3, T1/U, T2/V, T3/W, UD+, UDC- terminalsCable entriesFrame
Tightening
torque
Max wire size
(solid/ stran-
ded)
Min wire size
(solid/ stran-
ded)
1)
Øpcs
N·mmm
2
mm
2
mm
1.716.00.5233R3
5.670.06.0453R6
184 Technical data