10. Install the shroud onto the power cable connection terminals.
R8
R
6
R8 power cable connection if you detach the connectors
The power cable connection connectors of frame R8 are detachable. If you detach them,
you can connect the cables with cable lugs as follows. For UL installations, see also UL
listed cable lugs and tools (page 185) in the technical data.
Cable lug installation for T1/U, T2/V, T3/W, UDC+ and UDC-:
Remove the nut that attaches the connector to its terminal post and remove the
connector.
Alternative 1: Put the conductor to the connector. Tighten to a torque of 30 N·m
(22 lbf·ft). Put the connector back onto the post. Tighten the connector to 30 N·m
(22 lbf·ft).
Alternative 2: Attach a cable lug to the conductor. Put the cable lug onto the post.
Tighten the nut to a torque of 30 N·m (22 lbf·ft).