manner which produces a conductance equivalent to that which results from the
application of this table.
Minimum cross-sectional area of the corres-
ponding protective conductor
S
p
(mm
2
)
Cross-sectional area of the phase conduct-
ors
S (mm
2
)
S
1)
S 16
1616 < S 35
S/235 < S
1)
To comply with standard IEC/EN 61800-5-1:
use a protective earth conductor with a minimum cross-sectional area of 10 mm
2
Cu or 16 mm
2
Al (as an
alternative when aluminum cables are permitted),
or
use a second protective earth conductor of the same cross-sectional area as the original protective earth
conductor,
or
use a device that automatically disconnects the supply if the protective earth conductor is damaged.
If the protective earth conductor is separate (that is, it does not form part of the input power cable or the input
power cable enclosure), the minimum cross-sectional area must be:
2.5 mm
2
when the conductor is mechanically protected,
or
4 mm
2
when the conductor is not mechanically protected.
Typical power cable sizes
See the technical data.
Power cable types
Preferred power cable types
This section presents the preferred cable types. Make sure that the selected cable type
also complies with local/state/country electrical codes.
Use as motor cablingUse as input power cablingCable type
YesYes
PE
Symmetrical shielded (or ar-
mored) cable with three phase
conductors and concentric PE
conductor as shield (or armor)
64 Guidelines for planning the electrical installation