L1, L2, L3, T1/U, T2/V, T3/W, UD+, UDC- terminalsCable entriesFrame
Tightening
torque
Max wire size
(solid/ stran-
ded)
Min wire size
(solid/ stran-
ded)
1)
Øpcs
N·mmm
2
mm
2
mm
3015025453R8
1)
Note: Only copper cables are allowed for drive types up to -039A-4.
For tightening torques of grounding terminals, see section Connection
procedure (page 94).
Screwdrivers for the terminals of the main circuitFrame
Flat blade 0.6 x 3.5 mmR3
L1, L2, L3, T1/U, T2/V, T3/W, UD+, UDC- terminalsCable entriesFrame
Tightening
torque
Max wire size
(solid/ stran-
ded)
Min wire size
(solid/ stran-
ded)
Øpcs
lbf·ftAWGAWGin
1.36200.913R3
4.12/0101.773R6
22.530041.773R8
For tightening torques of grounding terminals, see section Connection
procedure (page 115).
■ UL listed cable lugs and tools
Crimping toolCompression lugWire size
kcmil/AWG
No. of crimpsTypeManufacturerTypeManufacturer
1TBM4SThomas &
Betts
E10731
54136
Thomas &
Betts
6
TBM45S
1MY29-3BurndyYAV6C-L2Burndy
2ILC-10IlscoCCL-6-38Ilsco
1TBM4SThomas &
Betts
54140Thomas &
Betts
4
1MY29-3BurndyYA4C-L4BOXBurndy
1MT-25IlscoCCL-4-38Ilsco
Technical data 185