EasyManua.ls Logo

ABB ACS880-11 - Continuous Motor Cable Shield;Conduit or Enclosure for Equipment on the Motor Cable

ABB ACS880-11
232 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
1
1
1
1
3
3
3
3
3
3
2
2
2
2
Input power cabling1
Motor cabling2
Conduit3
Continuous motor cable shield/conduit or enclosure for equipment on
the motor cable
To minimize the emission level when safety switches, contactors, connection boxes or
similar equipment are installed on the motor cable between the drive and the motor:
Install the equipment in a metal enclosure.
Use either a symmetrical shielded cable, or install the cabling in a metal conduit.
Make sure that there is a good and continuous galvanic connection in the
shield/conduit between drive and motor.
Connect the shield/conduit to the protective ground terminal of the drive and the
motor.
Guidelines for planning the electrical installation 71

Table of Contents

Other manuals for ABB ACS880-11

Related product manuals