UL (NEC)
3)
IEC
1)
Frame
size
Drive type
ACS880-
11-…
Cu cable typeAl cable type
2)
Cu cable type
AWG/kcmilmm
2
mm
2
43×353×25R6052A-5
33×503×35R6065A-5
23×703×35R6077A-5
1/03×703×50R8101A-5
3/03×953×95R8124A-5
4/03×1503×120R8156A-5
300MCM-3×150R8180A-5
1) The cable sizing is based on max. 9 cables laid on a cable ladder side by side, three
ladder type trays one on top of the other, ambient temperature 30 °C, PVC insulation,
surface temperature 70 °C (EN 60204-1 and IEC 60364-5-52/2001). For other conditions,
size the cables according to local safety regulations, appropriate input voltage and the
load current of the drive.
2) Aluminum cables must not be used with drives of frame size R3.
3) The cable sizing is based on NEC Table 310-16 for copper wires, 75 °C (167 °F) wire
insulation at 40 °C (104 °F) ambient temperature. Not more than three current-carrying
conductors in raceway or cable or earth (directly buried). For other conditions, size the
cables according to local safety regulations, appropriate input voltage and the load
current of the drive.
4) In the USA, aluminum cables must not be used.
Temperature: For IEC, select a cable rated for at least 70 °C maximum permissible
temperature of conductor in continuous use. For North America, power cables must be
rated for 75 °C (167 °F) or higher.
For surrounding air temperatures above 40 °C (104 °F) or frame R6 with option +B056
(UL Type 12), select a cable rated for at least 90 °C (194 °F) maximum permissible
temperature of conductor in continuous use.
Voltage: 600 V AC cable is accepted for up to 500 V AC.
Electrical power network specification
ACS880-11-xxxx-3 drives: 380…415 V AC 3-phase +10%…-15%. This
is indicated in the type designation label as typical input voltage level
3~400 V AC.
Voltage (U
1
)
ACS880-11-xxxx-5 drives: 380...500 V AC 3-phase +10%…-15%. This
is indicated in the type designation label as typical input voltage levels
3~400/480/500 V AC.
188 Technical data