EasyManua.ls Logo

ABB ACS880-11 - Connecting Motor Temperature Sensor to the Drive Via an Option Module; Protecting the Drive against Ground Faults; Residual Current Device Compatibility

ABB ACS880-11
232 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Connecting motor temperature sensor to the drive via an option module
This table shows:
option module types that you can use for the motor temperature sensor connection
insulation or isolation level that each option module forms between its temperature
sensor connector and other connectors
temperature sensor types that you can connect to each option module
temperature sensor insulation requirement in order to form, together with the
insulation of the option module, a reinforced insulation between the motor live parts
and the drive control unit.
Temperature sensor insula-
tion requirement
Temperature
sensor type
Option module
Pt100,
Pt1000
KTYPTCInsulation/IsolationType
Reinforced insulationxx-Galvanic isolation between
sensor connector and other
connectors (including drive
control unit connector)
FIO-11
Reinforced insulation-xxGalvanic isolation between
sensor connector and other
connectors (including drive
control unit connector)
FEN-xx
Basic insulation. Connectors of
option module other than
sensor connector must be left
unconnected.
xxxBasic insulation between
sensor connector and drive
control unit connector. No insu-
lation between sensor connect-
or and other I/O connectors.
FAIO-
01
No special requirement--xReinforced insulation between
sensor connector and other
connectors (including drive
control unit connector).
FPTC-
xx
1)
1)
Suitable for use in safety functions (SIL2 / PL c rated).
Protecting the drive against ground faults
The drive is equipped with an internal ground fault protective function to protect the unit
against ground faults in the motor and motor cable. This function is not a personnel
safety or a fire protection feature. See the firmware manual for more information.
Residual current device compatibility
The drive is suitable to be used with residual current devices of Type B.
76 Guidelines for planning the electrical installation