Requirement forNominal AC sup-
ply voltage
ABB du/dt and common mode filters, insulated N-end
motor bearings
Motor insulation
system
P
n
≥ 200 kW100 kW ≤ P
n
<
200 kW
P
n
< 100 kW
P
n
≥ 268 hp140 hp ≤ P
n
<
268 hp
P
n
< 140 hp
+ N + CMF+ N-Standard
U
n
≤ 500 V
+ du/dt + N + CMF+ du/dt + N+ du/dt
Standard
500 V < U
n
≤ 600
V
or
+ N + CMF+ N-Reinforced
+ du/dt + N + CMF+ du/dt + N+ du/dt
Reinforced
600 V < U
n
≤ 690
V
Additional requirements for non-ABB high-output and IP23 motors
The rated output power of high-output motors is higher than what is stated for the
particular frame size in EN 50347 (2001).
If you plan to use a non-ABB high-output motor or an IP23 motor, consider these
additional requirements for protecting the motor insulation and bearings in drive systems:
• If motor power is below 350 kW: Equip the drive and/or motor with the filters and/or
bearings according to the table below.
• If motor power is above 350 kW: Consult the motor manufacturer.
60 Guidelines for planning the electrical installation