To Previous Page IconTo Previous Page
Loading...
Allowed only for input cabling with phase
conductor cross-section less than 10 mm
2
(8 AWG)
PE
PE
8. Put the cable through the hole of the cable entry plate and attach the grommet to
the hole.
9. Connect the cables:
Ground the shield 360 degrees by tightening the clamp of the power cable
grounding shelf onto the stripped part of the cable.
Connect the twisted shield of the cable to the grounding terminal.
Connect the additional PE conductors (if any).
Connect the phase conductors of the motor cable to the T1/U, T2/V and T3/W
terminals and the phase conductors of the input cable to the L1, L2 and L3
terminals.
For frame R8: Install the common mode filter. For instructions, see Common
mode filter kit for ACS880-01 frame R7, and for ACS880-11, ACS880-31,
ACH580-31 and ACQ580-31 frame R8 (option +E208) installation instructions
(3AXD50000015179 [English]).
Tighten the screws to the torque given in the installation drawing below.
L1
,
L2
,
L3
,
T1/U
,
T2/V
,
T3/W: 1.7 N·m
1.7 N·m
1.7 N·m
1.7 N·m
L1
L2
L3
UDC+
UDC-
T1/U
T2/V
T3/W
R3
98 Electrical installation IEC