plate (option +H358), refer also to the instruction of the related non-ABB installation
accessories. For example, the Roxtec instructions or the instructions by the cable
gland manufacturer.
WARNING!
Obey the safety instructions of the drive. If you ignore them, injury or
death, or damage to the equipment can occur. If you are not a qualified
electrical professional, do not do installation, commissioning or
maintenance work.
1. Stop the drive and do the steps in section Electrical safety precautions (page 49)
before you start the work.
2. Open the door of the DC/DC converter cubicle and remove the shrouding (if any).
3. IP54 cabinet: Remove the rear horizontal cable support and the cable entry plate.
IP54 cabinet: Remove a sealing grommet from the cable entry plate for each cable.
Cut hole into the rubber grommet and slide it onto the cable.
4. Lead the cables inside the cabinet through the cable entry plate. If there are several
cables, use the rear 3 holes first.
IP54 cabinet: Attach the the sealing grommets to the cable entry plate. Attach
also the cable entry plate, and the cable support.
5. For each cable, strip off 3…5 cm (1.2 … 2 inches) of the outer insulation above the
cable entry plate. Strip also the end of the cable, and the end of the conductors.
Twist the shield to form a PE conductor, and mark it with yellow-green tape or
heat-shrink tubing.
6. For each cable, attach cable lugs at the end of the PE conductor (twisted shield)
and other conductors.
54 Electrical installation