7. Connect the phase conductors of the input cables to terminals L1/U1, L2/V1 and L3/W1
of the drive module. For the tightening torques, see the technical data.
8. Brake chopper option: Run the power cables from the brake chopper to the cabinet.
Ground the cable shield (if present) 360° at the entry plate. Connect the conductors to
the UDC+ and UDC- terminals. For the tightening torques, see the technical data.
Removing the control panel holder from the external control
unit
1. Disconnect the control panel cable from connector X13 on the control unit.
2. Loosen the mounting screws of the control panel holder and take the holder off.
Attaching the control cable clamp plate
Attach the control cable clamp plate either to the top or base of the control unit with four
screws as shown below.
Note: If you install the FSO-xx safety functions module above the control unit, fasten the
control cable clamp plate on the base of the control unit.
Electrical installation 103