Fuses (UL Recognized)
UL Recognized fuses for branch circuit protection per NEC are listed below. Check that
the operating time of the fuse is below 0.1 seconds. The operating time depends on the
fuse type, supply network impedance and the cross-sectional area, material and length of
the supply cable. The fuses must be of the “non-time delay” type. Obey local regulations.
Fuse
Input current
(A)
Drive type
ACS880-34-
Type DIN
43653
SizeManufacturerVA
U
N
= 400 V
170M54082Bussmann690400212246A-3
170M54102Bussmann690500257293A-3
170M64103Bussmann690630321363A-3
170M64113Bussmann690700401442A-3
170M64123Bussmann690800401505A-3
170M64143Bussmann6901000505585A-3
170M64143Bussmann6901000569650A-3
U
N
= 500 V
170M44101Bussmann690315169240A-5
170M54082Bussmann690400205260A-5
170M54102Bussmann690500249302A-5
170M64103Bussmann690630257361A-5
170M64113Bussmann690700321414A-5
170M64113Bussmann690700404460A-5
170M64123Bussmann690800455503A-5
U
N
= 690 V
170M44091Bussmann690250123142A-7
170M44101Bussmann690315149174A-7
170M54082Bussmann690400186210A-7
170M54102Bussmann690500232271A-7
170M64103Bussmann690630293330A-7
170M64113Bussmann690700330370A-7
170M64113Bussmann690700375430A-7
3AXD00000588487
Note:
See also Protecting the drive and input cable in short-circuits and against thermal
overload (page 86).
In multicable installations, install only one fuse per phase (not one fuse per conductor).
Fuses with higher current rating than the recommended ones must not be used. Fuses
with lower current rating can be used.
Fuses from other manufacturers can be used if they agree with the ratings and the
melting curve of the fuse does not exceed the melting curve of the fuse mentioned in
the table.
184 Technical data