US
2)
IEC
1)
Drive type
ACS880-34-
Al cable typeCu cable typeAl cable typeCu cable type
AWG/kcmilAWG/kcmilmm
2
mm
2
U
N
= 400 V
350 MCM or 2 × 2/0250 MCM or 2 × 12 × (3 × 95)2 × (3 × 50)246A-3
500 MCM or 2 × 3/0350 MCM or 2 × 2/02 × (3 × 120)2 × (3 × 70)293A-3
700 MCM or 2 × 4/0 or 3 × 2/0500 MCM or 2 × 3/03 × (3 × 95)3 × (3 × 50)363A-3
2 × 300 MCM or 3 × 3/0700 MCM or 2 × 4/0 or 3 × 2/03 × (3 × 120)3 × (3 × 70)442A-3
2 × 300 MCM or 3 × 3/0700 MCM or 2 × 4/0 or 3 × 2/03 × (3 × 120)3 × (3 × 70)505A-3
2 × 500 MCM or 3 × 250 MCM2 × 350 MCM or 3 × 4/03 × (3 × 150)3 × (3 × 120)585A-3
2 × 600 MCM or 3 × 300 MCM2 × 400 MCM or 3 × 4/03 × (3 × 185)3 × (3 × 120)650A-3
U
N
= 500 V
250 MCM or 2 × 13/02 × (3 × 70)1 × (3 × 120)240A-5
350 MCM or 2 × 2/0250 MCM or 2 × 13 × (3 × 70)2 × (3 × 50)260A-5
500 MCM or 2 × 3/0300 MCM or 2 × 1/03 × (3 × 70)2 × (3 × 70)302A-5
500 MCM or 2 × 3/0350 MCM or 2 × 2/03 × (3 × 70)2 × (3 × 120)361A-5
700 MCM or 2 × 4/0 or 3 × 2/0500 MCM or 2 × 3/02 × (3 × 150)3 × (3 × 50)414A-5
2 × 300 MCM or 3 × 3/0700 MCM or 2 × 4/0 or 3 × 2/03 × (3 × 120)3 × (3 × 70)460A-5
2 × 400 MCM or 3 × 4/02 × 250 MCM or 3 × 2/03 × (3 × 120)3 × (3 × 95)503A-5
U
N
= 690 V
3/01/02 × (3 × 50)1 × (3 × 70)142A-7
4/02/02 × (3 × 50)2 × (3 × 50)174A-7
300 MCM or 2 × 1/04/02 × (3 × 70)2 × (3 × 50)210A-7
400 MCM or 2 × 2/0300 MCM or 2 × 1/03 × (3 × 50)2 × (3 × 70)271A-7
600 MCM or 2 × 4/0 or 3 × 1/0400 MCM or 2 × 2/02 × (3 × 120)2 × (3 × 50)330A-7
700 MCM or 2 × 4/0 or 3 × 2/0500 MCM or 2 × 3/02 × (3 × 150)3 × (3 × 70)370A-7
2 × 300 MCM or 3 × 3/0700 MCM or 2 × 4/0 or 3 × 2/02 × (3 × 185)3 × (3 × 70)430A-7
3AXD00000588487
The cable sizing is based on max. 9 cables laid on a cable ladder side by side, three ladder type trays one
on top of the other, ambient temperature 30 °C (86 °F) PVC insulation, surface temperature 70 °C (158 °F)
(EN 60204-1 and IEC 60364-5-52). For other conditions, dimension the cables according to local safety
regulations, appropriate input voltage and the load current of the drive.
1)
The cable sizing is based on NEC Table 310-16 for copper wires, 75 °C (167 °F) wire insulation at 40 °C
(104 °F) ambient temperature. Not more than three current-carrying conductors in raceway or cable or earth
(directly buried). For other conditions, dimension the cables according to local safety regulations, appropriate
input voltage and the load current of the drive.
2)
Terminal and entry data for the power cables
The maximum accepted cable size is 4 × (3 × 240) mm
2
or 4 × (3 × 500 AWG). Screw size
for connecting busbars to the drive module input and output busbars: M12, tightening torque
50…75 N·m.
Technical data 187