The instructions and technical data which concern only certain optional selections are marked
with option codes, eg, +E208. The options included in the drive can be identified from the
option codes visible on the type designation label. The option selections are listed in section
Type designation key (page 39).
Quick installation, commissioning and operating flowchart
See chapter/sectionTask
Guidelines for planning the mechanical installa-
tion (page 51)
Plan the mechanical and electrical installation and ac-
quire the accessories needed (cables, fuses, etc.).
Examine the ambient conditions, ratings, required
cooling air flow, input power connection, compatibility
of the motor, motor connection, and other technical
data.
Guidelines for planning the electrical installa-
tion (page 71)
Technical data (page 175)
Resistor braking (page 227)
Option manual (if optional equipment is included)
Moving and unpacking (page 61)
Unpack and examine the units.
Make sure that all necessary optional modules and
equipment are present and correct.
Examining the delivery (page 68)
If the drive module has been non-operational for a year
or more, the converter DC link capacitors need to be
reformed. (Reforming the capacitors (page 165))
Only intact units can be started up.
Examining the installation site (page 61)
Examine the installation site. Attach the base of the
cabinet to the floor.
Ambient conditions (page 191)
Routing the cables (page 82)
Route the cables.
Measuring the insulation (page 94)
Measure the insulation of the supply cable, the motor
and the motor cable and the resistor cable (if present).
Installing the drive module and LCL filter module into
a cabinet (page 131)
Standard drive modules
Install the additional components into the cabinet: for
example, main disconnector, main contactor, main
AC fuses, etc..
Install the drive module into the cabinet.
Connect the motor cables to the drive module termin-
als.
Connect the brake resistor and DC connection cables
(if any) to the drive module terminals.
If the main disconnector is installed into the cabinet,
connect it to the drive module terminals and the input
power cabling to the disconnector.
Connect the cables from the drive module to the ex-
ternal control unit and install the control unit into the
cabinet.
Connecting the power cables and installing the
shrouds (page 133)
Connecting the external control unit to the drive mod-
ule (page 104)
Attaching the external control unit (page 106)
Manuals for any optional equipment