Single-channel connection
+24 V
OUT
SGND
IN2
K
IN1
1
2
Note:
Both STO inputs (IN1, IN2) must be connected to the activation switch. Otherwise, no SIL/PL classification
is given.
Pay special attention to avoiding any potential failure modes for the wiring. For example, use shielded cable.
For measures for fault exclusion of wiring, see eg. EN ISO 13849-2:2012, table D.4.
Drive1
Control unit2
Activation switchK
The Safe torque off function 215