Attaching the cabinet
WARNING!
Do not attach the cabinet by electric welding. ABB does not assume any liability
for damages caused by electric welding as the welding circuit can damage
electronic circuits in the cabinet.
Cabinet placement on a cable channel
Note the following when you plan to place the cabinet on a cable channel:
• The cabinet structure must be sturdy enough. If the whole cabinet base is not supported
from below, the cabinet weight will lie on the sections that the floor carries.
• Equip the cabinet with a sealed bottom plate and cable entries to ensure the degree of
protection and to prevent the cooling air flow from the cable channel into the cabinet.
Cabinet side view with a bottom plateThe supporting structure on a cable channel
Cubicle heaters
Use a cubicle heater if there is a risk of condensation in the cabinet. Although the primary
function of the heater is to keep the air dry, it may also be required for heating at low
temperatures.
Mounting the control panel on the cabinet door
You can use a mounting platform to mount the control panel on the cabinet door. Mounting
platforms for control panels are available as options from ABB. For more information, see
Code (English)Manual
3AUA0000100140
DPMP-01 mounting platform for control panels installation guide
3AUA0000136205
DPMP-02/03 mounting platform for control panels installation guide
3AXD50000308484
DPMP-04 and DPMP-05 mounting platform for control panels installation guide
Generic cabinet planning instructions 49