EasyManuals Logo

ABB ACS880-34 Series User Manual

ABB ACS880-34 Series
256 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #178 background imageLoading...
Page #178 background image
1500 m
1000 m
+25 °C +30 °C
+77 °F +86 °F
+40 °C
+104 °F
+35 °C
+95 °F
+20 °C
+68 °F
3300 ft
4921 ft
2000 m
6562 ft
2500 m
8202 ft
3000 m
9842 ft
3500 m
11429 ft
4000 m
13123 ft
1.00
0.95
0.85
0.90
0.80
Derating factor 1.00
Derating factor 0.95
Derating factor 0.90
Derating factor 0.85
Derating factor 0.80
Deratings for special settings in the drive control program
Enabling special settings in the drive control program can require output current derating.
Ex motor, sine filter, low noise
Table below gives the deratings for these cases:
drive is used with an ABB motor for explosive atmospheres (Ex) and EX motor in
parameter 95.15 Special HW settings is enabled
sine filter given in the selection table (see section Sine filters) is used and ABB sine
filter in parameter 95.15 Special HW settings is enabled
Low noise optimization is selected in parameter 97.09 Switching freq mode.
With other than recommended sine filters (see section Sine filters) and non-ABB Ex motors,
contact ABB.
Output ratings for special settingsDrive
type
ACS880-
34-
Low noise modeABB sine filterEx motor (ABB Ex motor)
Heavy-
duty
use
Light-
duty
use
Nominal useHeavy-
duty
use
Light-
duty
use
Nominal useHeavy-
duty
use
Light-
duty
use
Nominal use
I
Hd
I
Ld
P
N
I
N
I
Hd
I
Ld
P
N
I
N
I
Hd
I
Ld
P
N
I
N
AAkWAAAkWAAAkWA
U
N
= 400 V
180204132217185210132221196222132234246A-3
178 Technical data

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB ACS880-34 Series and is the answer not in the manual?

ABB ACS880-34 Series Specifications

General IconGeneral
Voltage Range380 V to 690 V
Control MethodDirect Torque Control (DTC)
Cooling MethodAir or liquid cooling
Protection ClassIP21
Communication ProtocolsModbus, Profibus, CANopen, Ethernet
Protection FeaturesOvercurrent, overvoltage, overtemperature, short circuit
Power Range0.55 to 5.6 MW

Related product manuals