min. 200 mm (8 in)
90°
*min. 500 mm (20 in)
1
2
3
3
2
1
4
min. 300 mm (12 in)
2
4
3
min. 300 mm (12 in)
*
Motor cable1
Input power cable2
Control cable3
Brake resistor or chopper cable (if any)4
■ General guidelines – North America
Make sure that the installation is in accordance with national and local codes. Obey these
general guidelines:
• Use separate conduits for the input power, motor, brake resistor (optional), and control
cabling.
• Use separate conduit for each motor cabling.
Guidelines for planning the electrical installation 83