Connecting the power cables
Connection diagram
INPUT
OUTPUT
U1
V1
W1
M
3 ~
L3/W1
UDC
-
UDC+
L3/W1
UDC-
UDC+
L2/V1
L1/U1
(PE) PE (PE)
L1
L2 L3
L1
L2
L3
1
2b
3
4
5
6
7
8
2a
9
4
PE
L1/U1
L2/V1
T1/U2
T2/V2
T3/W2
T1/U2
T2/V2
T3/W2
UDC-
L3/W1
L3/W1
ACS880-34
For alternatives, see section Selecting the main supply disconnecting device (page 71). In the installing
example of this chapter, the disconnecting device is not in the same cubicle with the drive module.
1
If a shielded cable is used (not required but recommended) and the conductivity of the shield is < 50%
of the conductivity of the phase conductor, use a separate PE cable (2a) or a cable with a grounding
conductor (2b).
2
ABB recommends 360-degree grounding at the cabinet entry if a shielded cable is used. Ground the
other end of the input cable shield or PE conductor at the distribution board.
3
Installation example with full cabling panels (option +H381) 139