1.5 Error Messages
350.0
351.5
350.0
351.5
350.0
351.5
350.0
351.5
350.0
351.5
350.0
351.5
350.0
351.5
Error/Action
Calibration Error
Turn mains power off and on again
(if the error persists contact the
Customer Support Organization).
Non-volatile Memory Error
x = 1: Processor Board Memory
x = 3: Power Supply Board Memory
Turn mains power off and on again
(if the error persists, check
configuration/setup settings).
A to D Converter Fault
The analog to digital converter is not
communicating correctly.
Input Value Over/Under Range
Auto-tune Error
Number displayed indicates the type
of error – see Table 2.1.
Cold Junction Failed
Cold junction sensor is faulty or has
not been fitted correctly.
Remote Set Point Failed
Input value is over or under-range.
Only appears if the remote set point
is displayed or in use.
External Ratio Fail
Input value is over or under-range. Only
when templates 14 to 17 are used
Position Feedback Fail
Input value is over- or under-range.
Only appears if output type set to
'
PFb' – motorized valve with feeback.
Valve Sticking
Motorized valve not moving at the
speed expected. Valve may be
sticking.
To clear the display:
Press the key
Press the key
Contact the Customer
Support Organization
Restore valid input
Press the key
Check connections or replace
if faulty.
Restore valid input
Restore valid input
Restore valid input
Check that the correct
Regulator Travel Time has
been set – see Section 4.5.
Check the valve.
Display
CAL
Err
9999
t.Err
1
StK
A-d
Err
Err
NVx
CJ.F
1
rAt.F
9999
350.0
351.5
rSP.F
9999
999