62
8
1.000
C.rtO
3.08
OFF
r.rtE
3.10
0
C.bIA
3.09
•1
•1
Actual (Ramping) Set Point Value
used by PID Algorithm*
0
100
200
300
1 Hour
Displayed Local Set Point Value
Time
PV
* e.g. Ramp Rate = 200 Increments/Hour
LEV3
SEt.P
…4.3 Level 3 – Set Points
…4 SET UP MODE
3.08...3.10
•1 Displayed only if a Cascade template is selected – see Section 5.2, Basic Configuration/ Template
Application.
Cascade Set Point Ratio
In automatic mode, the slave set point value is:
(ratio x master output) + bias.
[0.001 to 9.999]
Cascade Set Point Bias
[In engineering units]
Ramp Rate
[1 to 9999 engineering units per hour, or '
OFF']
The Ramping Set Point facility can be used to prevent a large
disturbance to the control output when the set point value is changed.
The rate set applies to both the local and the remote set points.
Return to top of page.