4.5.1 Valve Setup (Feedback Types)
4.5 Level 5 – Valve Setup
Note. Level 5 is applicable only for a motorized valve output type – see Section 5.2, Basic Configuration/
Output Type.
Fig. 4.3 Motorized Valve Output with Feedback – Schematic
Level 5 – Valve Setup
Note. To select this frame from anywhere in this page, press and
hold the
key for a few seconds.
Motorized Valve Ratio and Bias
Desired valve position = (Ratio x PID output) + Bias
Motorized Valve Ratio
[0.01 to 10.00]
Motorized Valve Bias
[–100.0 to 100.0%]
Motorized Valve Deadband
[0.0 to 100% of the position feedback span]
Example. If the valve is set to be driven to the 50% open position and
the deadband is set to 4%, the motor stops driving when the position
feedback is 48%. The deadband is between 48% and 52%.
Regulator Travel Time
The time entered is compared with the actual travel time. If the valve is
sticking an error message is generated.
[0 to 5000 seconds, 0 = no check]