81
5.5 Level 9 Set Point Configuration 9.06...9.11
5 CONFIGURATION MODE
Remote Set Point Fault Action
The action required when a fault occurs with the remote set point.
NONE No action
LOC Select local set point mode
dFLt Select local set point mode and set to the default value
Local Set Point Default Value
Set the value required for the local set point under remote set point fault
conditions.
[In engineering units]
Local Set Point Source 1
The source required to select local set point 1 (LSP1) as the current local
set point.
See Rear Fold-out/ Table C
– Digital Sources.
Local Set Point Source 2
The source required to select local set point 2 (LSP2) as the current local
set point.
See Rear Fold-out/ Table C
– Digital Sources.
Local Set Point Source 3
The source required to select local set point 3 (LSP3) as the current local
set point.
See Rear Fold-out/ Table C
– Digital Sources.
Local Set Point Source 4
The source required to select local set point 4 (LSP4) as the current local
set point.
See Rear Fold-out/ Table C
– Digital Sources.
Continued…
NONE
L.Sr2
9..09
NONE
L.Sr1
9..08
NONE
L.Sr3
NONE
L.Sr4
9.10
9.11
NONE
SP.FA
9..06
0.0
dF.SP
9..07
LSP1
LSP2
LSP3
LSP4
•2
•2
•2
•2
•1
•1
•1 Displayed only if a remote set point template is selected.
•2 A digital input becomes active when a volt-free contact is closed or a low TTL signal is applied.