5.5 Level 9 Set Point Configuration
Note. Level 9 is not applicable when an Indicator template (templates 7 and 8) or an Auto/Manual station
template (templates 3 and 4) is selected.
9.00...9.05
5 CONFIGURATION MODE
Level 9 Set Point Configuration
Note. To select this frame from anywhere in this page, press and
hold the
key for a few seconds.
Set Point Tracking Enable
Local Set Point Tracking – the local set point tracks the process variable
when manual mode is selected. Applies to master and slave set points
with cascade templates.
Remote Set Point Tracking – local set point tracks the remote set point
when in remote set point mode. If the controller is put into manual mode
the set point reverts from remote to local. Also applies to the local and
remote ratio when the ratio controller template is selected.
Set Point Limits
The set point limits define the maximum and minimum values to which
the local and/or remote set points can be adjusted.The set point limits do
not apply when in Manual mode with local set point tracking enabled. If
the set point is outside its limits when Automatic mode is selected, the
set point value can only be adjusted towards its limits. Once within the
limits they apply as normal.
Control Set Point (CSPT) or Master Set Point (M.SPT) High Limit
[–999 to 9999 in engineering units]
Control Set Point (CSPT) or Master Set Point (M.SPT) Low Limit
[–999 to 9999 in engineering units]
Note. Operator level adjustment of the set point can be disabled –
see Section 5.7, Operator Configuration/ Set Point Adjustment Enable.
High Limit for Slave Set Point
[In engineering units]
Low Limit for Slave Set Point
[In engineering units]
Continued…
•1 Displayed only if a Cascade template is selected.
•2 Not available with ratio controller and ratio station templates.
•3 Available only if a remote set point template is selected.