56
8
4 SET UP MODE
4.1 Introduction
To access the Set Up mode (Levels 2 to 5) the correct password must be entered in the security code frame.
Fig. 4.1 Set Up Mode – Overview
LEV2
Tuning
Cycle time, output 1 & 2
On/off hysteresis values
Proportional bands 1 to 4
Integral action times 1 to 4
Derivative action times 1 & 2
Manual reset value
Feedforward gain and bias
Control deadband
Heat Cool Output 1 & 2 Start
LEV3
Set Points
Local set point values 1 to 4
Slave set point value
Remote set point ratio/bias
Cascade set point ratio/bias
Ramp rate
LEV4
Alarm Trip Points
Alarm 1 to 8 trip points
LEV5
50
COdE
OFF
AtNE
LEV1
OPEr
LEV.t
LEV2
P.PrG
tUNE
LEV1
OPEr
Press
and hold
Invalid
password
LEV.5
VLVE
LEV6
APPL
Valid Configuration Password
Valid Set Up Password
Valid
Profile Configuration
Password
350.0
351.5
70
350.0
351.5
70
Motorized Valve Set Up
With feedback:
Feedback ratio/bias
Deadband
Regulator travel time
Boundless:
Deadband
Regulator travel time
350.0
351.5
70
350.0
351.5
70
tUNE
LEV.2
1.0
CYC.1
2.01
Frame number
2.xx – Level 2
3.xx – Level 3 etc.
Parameter
Parameter
adjustment
2.00
Default
value
350.0
351.5
70
Fig. 4.2 – Scroll Display Overview