t.09...t.13…3.5 Ramp/Soak Profile Program
Time Events
Up to four time-events can be assigned to the segment currently being
programmed – see Fig. 3.7on page 29.
Press the
key to turn event 1 ON.
Press the
key to turn event 1 OFF.
Press the
key to advance to the next event.
Example. '12-4' indicates time events 1, 2, and 4 are active during this
segment and time event 3 is inactive
Repeat Program Profile
[0 to 99 or '
INFN']
Note. If 1 is selected, the program runs twice; if 99 is selected, the
program runs 100 times in total.
If '
INFN' (infinity) is selected, the program is repeated until stopped by
the operator.
Guaranteed Ramp Hysteresis
[0.001 and 9999 in engineering units or '0' if no deviation from the profile
is allowed]
Guaranteed Soak Hysteresis
[0.001 and 9999 in engineering units or '0' if no deviation from the profile
is allowed]
Program Source
The program source is leading edge triggered i.e. the active logic state
can be removed after the function is selected.
See Rear Fold-out/Table C,
Digital Sources.
Return to Select Program frame.
3 PROFILES…
•1 A digital input becomes active when a volt-free contact is closed or a low TTL signal is applied.