…5.3 Level 7 – Analog Inputs
1000
En2.H
7..11
0
dP.2
7..10
C
UNt2
7.09
2
tYP2
7.08
0
En2.L
7.12
•1
•2
UP
bsd.2
7.13
0
FLt.2
7.14
7.08...7.14
Analog Input Type & Electrical Range (I/P2)
Note. THC inputs can only be used on I/P2 if I/P1 is also set to THC.
Temperature Units (I/P2)
C – THC readings displayed in °C
F – THC readings displayed in °F
Decimal Places (Engineering Range, I/P2)
0 – XXXX
1 – XXX.X
2 – XX.XX
3 – X.XXX
Engineering High (I/P2)
[–999 to 9999]
Note. This parameter defaults to the maximum allowed value
when THC input type is selected – see Table 5.1.
Engineering Low (I/P2)
[–999 to 9999]
Note. This parameter defaults to the minimum allowed value when
THC input is selected – see Table 5.1.
Broken Sensor Drive (I/P2)
NONE– No action. Actual input values remain valid.
UP – Input driven to the maximum upscale value (999)
dN – Input driven to the minimum downscale value (–999)
Filter Time Constant (I/P2)
The input values are averaged over the time set.
[0 to 60 seconds]
Continued…
…5 CONFIGURATION MODE
•1 Frames 7.09 to 7.14 are not displayed if Analog Input Type 2 is set to 'OFF'.
•2 Displayed only if THC input type is selected.