73
5.3 Level 7 Analog Inputs 7.04...7.07
Engineering High (I/P1)
[–999 to 9999]
Note. This parameter defaults to the maximum allowed value
when THC or RTD inputs are selected – see Table 5.1.
Table 5.1 Engineering Limits, THC & RTD Inputs
Engineering Low (I/P1)
[–999 to 9999]
Note. This parameter defaults to the minimum allowed value when
THC or RTD inputs are selected – see Table 5.1.
Broken Sensor Drive (I/P1)
NONE No action. Actual input values remain valid.
UP Input driven to the maximum upscale value (999)
dN Input driven to the minimum downscale value (–999)
In the event of a fault being detected on the input, the input is driven in
the direction selected.
Input Filter Time Constant (I/P1)
The input values are averaged over the time set.
[0 to 60 seconds]
Continued…
5 CONFIGURATION MODE
0
FLt.1
7.07
1000
En1.H
7.04
0
EnI.L
UP
b.Sd1
7.05
7.06
DTR/CHT
epyT
°C °F
.niM.xaMnapS.niM.niM.xaMnapS.niM
BepyT81–0081017027238721
EepyT001–00954841–256118
JepyT001–00905841–256109
KepyT001–003156841–2732711
LepyT001–00905841–256109
NepyT002–003109823–2732261
S&RepyT81–007102302903675
TepyT052–00306814–275801
001tP052–00652823–211154