61
8
SEtP
LEV.3
3.00
1.000
rAtO
0
BIAS
3.06
3.07
400
LSP4
3.04
200
LSP2
3.02
500
LSP1
3.01
•1
•2
•4
•4
•1
•2
300
S.SPt
3.05
•3
•1
3.00...3.07
4 SET UP MODE
•1 Not displayed for ratio controller or ratio station templates.
•2 Displayed only if a local set point source is selected – see Section 5.5, Set Point Configuration/ Local/Remote
Set Point Source.
•3 Displayed only if a cascade template is selected.
•4 Displayed only for templates with a remote set point.
4.3 Level 3 Set Points
Note. Level 3 is not applicable if Auto/Manual Station or Indicator templates are selected.
Level 3 Set Points
Note. To select this frame from anywhere in this page, press and
hold the
key for a few seconds.
Local Set Point Value 1
Set the default local set point value.
[Within set point high and low limits, in engineering units – see Level 9]
Local Set Point Values 2 to 4
[Within set point high and low limits, in engineering units – see Level 9]
Cascade Slave Set Point Value
Set the slave set point value.
[Within slave set point high and low limits, in engineering units]
Only adjustable in Manual mode.
Remote Set Point Ratio
The remote set point value is
(ratio x remote set point input) + bias.
[0.001 to 9.999]
Remote Set Point Bias
[In engineering units]
Continued…