117
APPENDIX A CONTROL TEMPLATES
Process Variable
Master Output
ao1
•1
•2
•1 Template 3 only. Alarm A1 trip value can be set to give the desired low signal detection
•2 Template 4 only
Digital Select
Manual Output
I/P2
Low Signal Select
(Alarm A1)
OP1
di.1
Auto/Manual
Select
I/P1
A2.2 Auto/Manual Station (Templates 3 and 4)
The Auto/manual Station provides a backup for a Master controller. In normal operation the COMMANDER 350’s current output follows the master
controller’s output value. A fault in the master system can be identified either by detecting a low signal on the master output
(template 3) or via a digital signal
(template 4). When a fault is detected the COMMANDER 350 selects manual mode with its output either set to the last valid maste
r output value or to a
configured output value – see Section 4.6/ Control Configuration/ Configured Output 1. When the master signal is restored or th
e digital input returns to its
normal state the COMMANDER 350 switches back to auto mode (i.e. COMMANDER 350 output = master output).
The auto/manual station can be used in series or in parallel with the master output signal – see Fig. A1. Parallel operation is
achieved by using relay 1 in
the COMMANDER 350 to energize an external relay (with suitable changeover contacts for switching low level signals) which selec
ts the output to be routed
to the actuator.