II K 4-46
Overview of Software
ParNo. Parameter name and significance Min Max Default Unit (1)
custom
setting
Grp 1 Motor Settings (continued)
1.11 Net Fail Time
During this time the supply voltage must return to a
value higher than Net Underv Trip (1.10). Otherwise
an undervoltage trip will be generated.
0 = restart prevented. In case of mains under-
voltage the drive will switch off with a fault
message.
>0 = automatic restart of the drive if the mains
voltage recovers within the set time.
(U
line>
result of (1.10))
0.0 10.0 0.0 s x
1.12 Cur Lim Speed
Speed-dependent current limitation. From this
speed value onward, the armature current will be
reduced to a proportional basis of 1/n.
Cur Lim Speed > Max Speed = no speed depend
current limit.
Cur Lim Speed < Max Speed = speed depend
current limitation
100 6500 6500 rpm x
(1) no chan