Start-up 35
06 X2 MDI/MDIX Defines the cable type connected to the
port.
The auto MDI/MDIX detection feature is
enabled by default. For each port, you can
disable auto MDI/MDIX and designate the
port as MDI port or designate the port as
MDIX port.
Connect MDI port to MDIX port via straight-
through twisted pair cabling. Both MDI-to-
MDI and MDIX-to-MDIX connections use
crossover twisted pair cabling.
0 = Auto
0 = Auto Auto detect.
1 = MDI Designates the port as MDI port.
2 = MDIX Designates the port as MDIX port.
07
25
Reserved These parameters are not used by the
adapter module.
N/A
26 Restore def conf Reverts the module to the factory settings
by restoring the default values of the
CANopen objects and the configuration
parameters. The object values that have
been stored to the non-volatile memory are
also erased.
When this parameter is set to 1 = Yes, the
default values are restored at the next
power-up or when configuration
parameters are validated with parameter
27 FBA A/B par refresh.
0 = No
0 = No Do not restore default settings.
1 = Yes Restore default settings.
27 FBA A/B par
refresh
Validates any changed adapter module
configuration parameter settings. After
refreshing, the value reverts automatically
to 0 = Done.
Note: This parameter cannot be changed
while the drive is running.
0 = Done
0 = Done Refreshing done
1 = Refresh /
Configure
Refreshing
No. Name/Value Description Default