Parameterization
82 FSM4000 D184B140U02
Submenu/parameter Value range Comment
Submenu Set the time-out limits and alarm behavior for values over
or under the electrode balance.
The electrode balance is calculated as the ratio between
the electrode AC voltages E1/E2. This value is displayed
in [%]. If the electrode voltage E2 is larger than E1, the
value is assigned a minus sign and the ratio E2/E1 is
displayed.
Alarm Elec Bal
Min. value 100 ... 300 Lower range limit for alarm.
0.0 %
Max. value 100 ... 300 Upper range limit for alarm.
300.0 %
Message Off, warning, error Defines the alarm behavior.
Off Note: To properly display the electrode voltage, the
electrode zero must be adjusted. For additional
information, see "Submenu Adjustment" on page 85.
Submenu Set the time-out limits and alarm behavior for values over
or under the magnetic linearity.
Alarm Mag Lin
Min. value 0 ... 100 Lower range limit for alarm.
0.0 %
Max. value 0 ... 100 Upper range limit for alarm.
100.0 %
Message Off, warning, error Defines the alarm behavior.
Off Note: If magnetic linearity is being measured (at least
every 5 minutes), the most recently acquired flowrate
during the measurement is retained (approx. 2 s).
Submenu Set the time-out limits and alarm behavior for values over
or under the signal-to-noise ratio.
Alarm SNR
Min. value 0 ... 100 Lower range limit for alarm.
0.0 %
Max. value 0 ... 100 Upper range limit for alarm.
100.0 %
Message Off, warning, error Defines the alarm behavior.
Off