ABB i-bus
®
KNX
Commissioning
FCA/S 1.x.x.1 | 2CDC508134D0202 235
communication object name
Input a: Temperature sensor
As soon as the set threshold value is exceeded or below the limit, it is possible to send a
1-bit value [0/1] EIS 1 DPT 1.001
1-byte value [0...+255] EIS 6 DPT 5.001
.
The object value depends on the data type of the threshold object (1-bit, 1-byte). The parameter can be found in Parameter
window a: Threshold 1, p. 199.
Change Threshold 1 lower limit
Input a: Temperature sensor
Change Threshold 1 upper limit
Input a: Temperature sensor
The upper and lower limits of threshold 1 can be changed via the bus.
The data type of these communication objects depends on the set data type of the communication object Output value –
Input a.
The lower limit should be selected to be lower than the upper limit.
Input a: Temperature sensor
See communication object 93
Change Threshold 2 lower limit
Input a: Temperature sensor
See communication object 94
Change Threshold 2 upper limit
Input a: Temperature sensor
See communication object 95