ABB i-bus
®
KNX
Parameters
146 2CDC508198D0211 Rev. A | AC/S 1.x.1
KNX to BACnet
The value received in the group object is output in the BACnet object using this template. The value
cannot be changed by BACnet. This value is also output on the web user interface and on the ASM output
socket for linking to other modules.
The settings for the ASM socket, web user interface, KNX and BACnet are set automatically as follows:
Main data point type
Data point type
Definition of the data point type that is transferred between the interfaces.
You will find further information on the data point types in chapter 4.7 Data point types
.
Use value after restart
This parameter defines which value is output in the BACnet object, on the web user interface and the ASM
socket after starting the application controller until a new value is received in the group object.
• Last value: The last value before device start is saved and reused. The value parameterized further
down in Initial value is used after the first download of the module to the application controller.
• Initial value: The value described further down in Initial value is used.