ABB i-bus
®
KNX
Parameters
186 2CDC508198D0211 Rev. A | AC/S 1.x.1
Selection of all options except Display:
Dependent parameter(s):
Room setpoint temperature type
Absolute setpoint temperatures
Relative setpoint temperatures
This parameter specifies whether the room thermostat uses absolute or relative room setpoint
temperatures. This setting does not affect the indication on the web user interface.
• Absolute setpoint temperatures: The room thermostat uses absolute room setpoint
temperatures e.g. 23 °C.
For the new master/slave interface a group object of type DPT 9.001 is used.
For the old master/slave interface a group object of type DPT 6.010 is used.
• Relative setpoint temperatures: The room thermostat uses relative room setpoint temperatures
e.g. +3 K.
For the new master/slave interface a group object of type DPT 9.002 is used.
For the old master/slave interface a group object of type DPT 6.010 is used.