AC/S 1.x.1 | 2CDC508198D0211 Rev. A 191
Fan coil unit, fan speed
Options:
Display
Display+set (slave) DPT 5.001
Display+set (slave) 5.010
This parameter specifies whether the fan speed set by the room thermostat is only to be displayed
on the web user interface, or it can also be changed by the user. The current value is output on the
ASM output socket and in a BACnet object.
Display: The fan speed is only displayed on the web user interface and cannot be changed.
Display+set (slave) DPT 5.001: The fan speed can be changed on the web user interface.
This setting functions only with ABB and Busch-Jaeger devices with the new master/slave
interface with group objects of type DPT 5.001
Display+set (slave) DPT 5.010: The fan speed can be changed on the web user interface.
This setting functions only with ABB and Busch-Jaeger devices with the old master/slave
interface with group objects of type DPT 5.010.
Selection of Display or Display+set (slave) DPT 5.001 option:
Dependent parameter(s):
Fan coil unit, type of fan
Options:
On/Off
3 stages
5 stages
Continuous fan 0...100%
Setting for the fan type. This setting must match the settings in the room thermostat.
On/Off: Not a multiple stage fan type. The fan can only be switched on and off
3 stages: Fan with 3 stages (0,1,2,3)
5 stages: Fan with 5 stages (0,1,2,3,4,5)
Continuous fan 0...100%: Continuous fan