ABB i-bus
®
KNX
Parameters
AC/S 1.x.1 | 2CDC508198D0211 Rev. A 269
Object name
Data type
Room involvement DPT 9.002
The module has this output socket if the
Yes
option is selected for the
Supply temperature control
parameter, the
Calculated
weather compensated option is selected for the Supply setpoint temperature source parameter and the Yes option is selected
for the Room involvement parameter.
Outputs of current value by which the supply setpoint temperature is increased or reduced by the Room involvement function.
Signal value: -670760...670760 K
Max. room setpoint temperature
DPT 9.001
This module has this output socket if the Yes option is selected for the Supply temperature control parameter, the Calculated
weather compensated option is selected for the Supply setpoint temperature source parameter and the Based on the current
room setpoint temperatures option is selected for the Economy mode parameter.
Outputs the highest room setpoint temperature that is present on the ASM input socket and that is used by the Economy mode
function.
Signal value: -273...670760 °C

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB i-bus KNX AC/S 1.x.1 Series and is the answer not in the manual?

ABB i-bus KNX AC/S 1.x.1 Series Specifications

General IconGeneral
BrandABB
Modeli-bus KNX AC/S 1.x.1 Series
CategoryController
LanguageEnglish

Related product manuals