ABB i-bus
®
KNX
Parameters
AC/S 1.x.1 | 2CDC508198D0211 Rev. A 273
Name (can be changed separately)
Input: Pump A fault Heating distribution circuit 1 bit
DPT 1.011
C, W, T
The module has this group object if the Yes option is selected for the Pump display pump fault status parameter.
The fault state of the pump can be received via this group object and evaluated by the device
Telegram value: 0 = Inactive
1 = Active
Input: Pump A operating status (Off/On)
Heating distribution circuit
DPT 1.011
The module has this group object if the Yes option is selected for the Pump display operating status parameter.
Input for the operating status (Off/On) provided by the pump. On pumps with their own control, this operating status can differ
from the operating status of the heating distribution circuit controller.
Telegram value: 0 = Inactive
1 = Active
In-/Output: Pump A override
disable/enable
Heating distribution circuit 1 bit
DPT 1.003
C, R, W, T
The module has this group object if the
Yes
option is selected for the
Override by WebUI
This object activates/deactivates the pump override for the heating distribution circuit controller.
1 = Enabled
In-/Output: Pump A override value
Heating distribution circuit
DPT 1.001
The module has this group object
if the Yes option is selected for the Override by WebUI parameter.
This object specifies the state with which the heating distribution circuit's pump is overridden if the pump override is active.
Telegram value: 0 = Off
1 = On