Parameters
274 2CDC508198D0211 Rev. A | AC/S 1.x.1
Name (can be changed separately)
Input: Pump B fault Heating distribution circuit 1 bit
DPT 1.011
C, W, T
The module has this group object if the Yes option is selected for the Double pump parameter and the Yes option is selected
for the Pump display pump fault status parameter.
The fault state of the second pump can be received via this group object and evaluated by the device
Telegram value: 0 = Inactive
1 = Active
In-/Output: Pump B override
disable/enable
Heating distribution circuit 1 bit
DPT 1.003
C, R, W, T
The module has this group object if the Yes option is selected for the Double pump parameter and the Yes option is selected
for the Override by WebUI parameter.
This object activates/deactivates the second pump override for the heating distribution circuit controller.
Telegram value: 0 = Disabled
1 = Enabled
In-/Output: Pump B override value
Heating distribution circuit
DPT 1.001
The module has this group object if the
Yes
option is selected for the
Double pump
Yes
for the Override by WebUI parameter.
This object specifies the state with which the heating distribution circuit's second pump is overridden if the second pump
override is active.
Telegram value: 0 = Off
1 = On
Input: Pump B repair switch status Heating distribution circuit 1 bit
DPT 1.011
C, W, T
The module has this group object if the Yes option is selected for the Double pump parameter and the Yes option is selected
for the Display pump repair switch status parameter.
The status of the repair switch for the second pump can be received via this group object and evaluated by the device.
Telegram value: 0 = Inactive
1 = Active