ABB i-bus
®
KNX
Parameters
AC/S 1.x.1 | 2CDC508198D0211 Rev. A 285
condition
Heating distribution circuit: Valve override control value
The module has this BACnet output object if the 3-way valve (mixing valve) option or the 2-way valve option is selected for the
Valve type parameter and the Yes option is selected for the Valve override disable/enable parameter.
Outputs the value used to override the heating distribution circuit's valve if the override is active.
Signal value: 0…100 %
Heating distribution circuit: Status Valve purge
The module has this BACnet output object if the 3-way valve (mixing valve) option or the 2-way valve option is selected for the
Valve type parameter and the Yes option is selected for the Status Valve purge
parameter.
Outputs the status as to whether the heating distribution circuit controller is actually undertaking a valve purge. This value is
received from the heating distribution circuit controller linked via the related module group object.
1 = Active