ABB i-bus
®
KNX
Parameters
320 2CDC508198D0211 Rev. A | AC/S 1.x.1
Name (can be changed separately)
Input: Heat generator operating status Heat generator 1 bit
DPT 1.011
C, W, T
The module has this group object if the Yes option is selected for the Show operating status parameter.
Input for the operating status (Off/On) provided by the heat generator. Due to the control integrated into the heat generator,
this status may differ from the operating status specified by this module.
Telegram value: 0 = Inactive
1 = Active
Input: Heat generator failure status Heat generator 1 bit
DPT 1.011
C, W, T
The module has this group object if the Yes option is selected for the Show fault status parameter.
Input for the fault status provided by the heat generator.
1 = Active
In-/Output: Pump override disable/enable
DPT 1.003
The module has this group object if the Yes option is selected for the Override by WebUI parameter.
This object activates/deactivates the override of the heat generator's pump.
Telegram value: 0 = Disabled
1 = Enabled
In-/Output: Pump override value Heat generator 1 bit
DPT 1.001
C, R, W, T
The module has this group object if the
Yes
option is selected for the
Override by WebUI
This object specifies the state with which the heat generator's pump is overridden if the pump override is active.
1 = On